/content/advancedmaterials/us/en/search-results.html

Genetron® HFCs

Genetron® 23 - (R-23)

A specialty low temperature refrigerant that may be used to replace R-13 and R-503 in the low stage of cascade systems. For new equipment and retrofits.

Overview
A specialty low temperature refrigerant that may be used to replace R-13 and R-503 in the low stage of cascade systems. For new equipment and retrofits.
Specifications

General Information

  • Application
    • Commercial Refrigeration
  • ASHRAE Number
    • R-23
  • Brand
    • Genetron®
  • Chemical Name
    • Trifluoromethane
  • Linear Formula
    • CHF3
  • Refrigerant Class
    • HFC
  • Refrigerant Type
    • Single component fluid
  • Substitutes
    • CFC-13, R-503
  • Typical Lubricant
    • POE

Physical Properties

  • Critical Pressure
    • 700.82 psia
  • Molecular Weight
    • 70 lbm/lbmol
  • Saturated Liquid Density
    • 77.6 lb/ft3 at -30 °F
  • Specific Heat of Liquid
    • 0.34 at -30 °F
  • Specific Heat of Vapor
    • 0.13 at -30 °F

Temperature

  • Boiling Point/Range
    • -115.6 °F at 1 Atm
  • Critical Temperature
    • 79.057 °F (ASTM D-1321)
  • Freezing Point
    • -247 °F at 1 Atm

Safety & Environment

  • Flammable Range
    • None, %vol. in air (Based on ASHRAE Standard 34 with Match Ignition)

Standards & Approvals

  • ASHRAE Safety Classification
    • Not classified

General Information

  • Application
    • Commercial Refrigeration
  • ASHRAE Number
    • R-23
  • Brand
    • Genetron®
  • Chemical Name
    • Trifluoromethane
  • Linear Formula
    • CHF3
  • Refrigerant Class
    • HFC
  • Refrigerant Type
    • Single component fluid
  • Substitutes
    • CFC-13, R-503
  • Typical Lubricant
    • POE

Physical Properties

  • Critical Pressure
    • 700.82 psia
  • Molecular Weight
    • 70 lbm/lbmol
  • Saturated Liquid Density
    • 77.6 lb/ft3 at -30 °F
  • Specific Heat of Liquid
    • 0.34 at -30 °F
  • Specific Heat of Vapor
    • 0.13 at -30 °F

Temperature

  • Boiling Point/Range
    • -115.6 °F at 1 Atm
  • Critical Temperature
    • 79.057 °F (ASTM D-1321)
  • Freezing Point
    • -247 °F at 1 Atm

Safety & Environment

  • Flammable Range
    • None, %vol. in air (Based on ASHRAE Standard 34 with Match Ignition)

Standards & Approvals

  • ASHRAE Safety Classification
    • Not classified
  • Brand : Genetron®
  • Refrigerant Class : HFC
  • Chemical Name : Trifluoromethane
  • Linear Formula : CHF3
  • Substitutes : CFC-13, R-503
  • Application : Commercial Refrigeration
  • ASHRAE Number : R-23
  • Typical Lubricant : POE
  • Refrigerant Type : Single component fluid
  • Molecular Weight : 70 lbm/lbmol
  • Specific Heat of Liquid : 0.34 at -30 °F
  • Specific Heat of Vapor : 0.13 at -30 °F
  • Saturated Liquid Density : 77.6 lb/ft3 at -30 °F
  • Critical Pressure : 700.82 psia
  • Freezing Point : -247 °F at 1 Atm
  • Critical Temperature : 79.057 °F (ASTM D-1321)
  • Boiling Point/Range : -115.6 °F at 1 Atm
  • Flammable Range : None, %vol. in air (Based on ASHRAE Standard 34 with Match Ignition)
  • ASHRAE Safety Classification : Not classified